自动遮阳功能模块用于控制遮阳设备,如百叶窗、卷帘、窗帘或遮阳篷。
除了手动操作外,还可以根据日照和室温,结合“智能房间控制器”,实现遮阳的自动化。
目录
- 输入
- 输出
- 参数
- 偏好
- 遮阳设备的类型
- 示例编程
- 功能描述
- 方向参数
- 起始/结束偏移量
- 齿隙时长
- 板条调整
- 完全移动、末端位置和剩磁
- 用于设置末端位置的功能
- 通过用户界面启用昼夜节律
- 时刻表
- 历史记录
输入↑
缩写 | 总结 | 描述 | 单元 | 数值范围 |
---|---|---|---|---|
Tg | Toggle | 在开、停、关之间切换。 用于单按键控制。 |
- | 0/1 |
Po | Partial open with push & hold | 通过推动&保持住实现部分开启 | - | 0/1 |
Pc | Partial close with push & hold | 通过推动&保持住实现部分关闭 | - | 0/1 |
Co | Complete open | 如果在运动中,则停止。 | - | 0/1 |
Cc | Complete close | 如果在运动中,则停止。 | - | 0/1 |
So | Slightly open | 软百叶窗完全关闭,并根据参数(Rd)在水平位置移动板条。 卷帘、窗帘和遮阳篷根据参数(Rd)移动到位置。 |
- | 0/1 |
Sps | Sun position automatic start | Activates the sun position automatic when On at the beginning of the shading period, or also with a pulse during the shading period. The sun position automatic is deactivated for the rest of the day, if block is operated manually. Pulse on (Spr) followed by a rising edge on (Sps) or pulse on (Spr) while (Sps) is active, restarts the sun position automatic. |
- | 0/1 |
DisSp | Disable sun position automatic | On 时,停用“太阳位置自动”。 | - | 0/1 |
Spr | Sun position automatic restart | Pulse followed by a rising edge at input (Sps) or pulse while input (Sps) is active, restarts the sun position automatic. | - | 0/1 |
Wa | Wind alarm | 将遮阳移动到参数(Wap)设定的风暴预警位置,并锁定模块。用于风暴保护。风暴预警不是人工操作。 所连接的传感器名称在用户界面中使用的名称。 |
- | 0/1 |
Dwc | Door/window contact | On 时,完全打开遮阳,并锁定该模块。 仍可以通过 App 进行手动控制。 |
- | 0/1 |
Off | Off | 脉冲停止运动。On 时锁定模块。 主导性输入。 |
- | 0/1 |
Pos | Position of shading | 将遮阳移到指定的位置。 | % | 0...100 |
Slat | Position of slats | 将板条移到指定位置。 此输入仅在某些配置中可见。 |
% | 0...100 |
T5 | T5 control | 按键1:完全打开 按键4:完全关闭 |
- | ∞ |
DisPc | Disable periphery control | On 时停用输入 Tg、Po、Pc、Co、Cc、So、T5。(如童锁、清洁) 仍可以通过用户界面进行控制。 |
- | 0/1 |
输出↑
缩写 | 总结 | 描述 | 数值范围 |
---|---|---|---|
Op | Open | 打开 此输出仅在某些配置中可见。 |
0/1 |
Cl | Close | 关闭 此输出仅在某些配置中可见。 |
0/1 |
Pos | Position of shading | 遮阳位置(0.0 = 开启,1.0 = 关闭) | 0...1 |
Slat | Position of slats | 板条位置(0.0=水平,1.0=垂直) 此输出仅在某些配置中可见。 |
0...1 |
Sp | Sun position automatic | On,如果输入(Sps) = 1 且输入(DisSp) = 0......并且如果勾选了 "使用阳光变量 "的设置,而且阳光晴朗。 或者应用程序中基于太阳位置的自动化被打开。 |
0/1 |
Wds | Wind, door/window contact state | 当输入(Wa)或输入(Dwc)为1时激活。 | 0/1 |
Off | Off | 当输入(Off)为1时激活。 | 0/1 |
AQpp | Command output | 与特定设备一起使用。 命令 * 1000000 + 百叶窗位置(%)*1000 + 板条位置(°)。 命令0 = 停止,1 = 百叶窗位置+板条位置,2 = 只有百叶窗位置,3 = 只有板条位置。 此输出仅在某些配置中可见。 |
0/1 |
AC | API Connector | 基于 API 的智能连接端口。 API Commands |
- |
参数↑
缩写 | 总结 | 描述 | 单元 | 数值范围 | 默认值 |
---|---|---|---|---|---|
Type | Shading type | 遮阳设备的类型: 0 = 百叶窗 1 = 卷帘 2 = 双开窗帘 3 = Schlotterer Retrolux 4 =左开窗帘$BR$$5 = 右开窗帘$BR$$6 = 遮阳棚 |
- | 0...6 | 0 |
Wap | Wind alarm position | 0 = 完全开放 1 = 完全关闭 |
- | 0/1 | 0 |
Spe | Sun position automatic end action | 0 = 无操作 1 = 完全打开 2 = 完全关闭 3 = 设置板条水平 |
- | 0...3 | 1 |
Tlc | Time long-click | 在输入端(Po)、(Pc)上用于完全打开/关闭的长按时长。 如果你喜欢双击,那么设置值>(Opd)或(Cld)。 0 = 总是开启完整的行程。 |
s | 0...∞ | 3 |
Opd | Opening duration | 开启时长 | s | 0...∞ | 75 |
Cld | Closing duration | 关闭时长 | s | 0...∞ | 70 |
Mld | Motor lock duration | 换向时的电机锁定时间。 | s | 0...∞ | 0,5 |
Tdc | Time double-click | 输入端(Po)、(Pc)上用于完全打开/关闭的双击时长。 0 = 不使用 |
s | 0...∞ | 0,3 |
Rd | Return duration | 软百叶窗:直到板条水平对齐的返回时长。 卷帘、窗帘、 遮阳棚:为输入(So)设置位置,范围为从开启[0.0]到关闭[1.0]。 |
s | 0.1...∞ | 0,8 |
Bldo | Backlash duration opposite | 向相反方向移动时的齿隙时长。 此参数仅在某些配置中可见。 |
s | 0...∞ | 0,15 |
Bld | Backlash duration | 向相同方向移动的齿隙时长。 此参数仅在某些配置中可见。 |
s | 0...∞ | 0 |
minTd | Minimum travel duration | 脉冲输入(Po)或(Pc)时的最小行程时间。 | s | 0...∞ | 0,4 |
Dir | Compass direction | 窗口的指南针方向: 0=北 90=东 180=南 270=西 -1=未配置 |
° | -1...360 | -1 |
Dts | Direction tolerance start | 当太阳进入遮阳区域时,用于“太阳位置自动”的方向公差。 | ° | 0...90 | 85 |
Dte | Direction tolerance end | 当太阳离开遮阳区域时,用于“太阳位置自动”的方向公差。 | ° | 0...90 | 85 |
Sw | Slat width | 板条的宽度。 此参数仅在某些配置中可见。 |
mm | 0...∞ | 70 |
Sd | Slat distance | 两个水平板条之间的距离。 此参数仅在某些配置中可见。 |
mm | 0...∞ | 60 |
Spm | Sun position automatic mode | 0 = Optimal brightness - no direct sunlight, with as much light as possible. Automatic remains off with closed shading. If the input (Sps) is active, a pulse on (Spr) restarts the sun position automatic. 1 = Optimal cooling - blocks even more solar radiation, but also results in lower brightness. Automatic remains off with closed shading. If the input (Sps) is active, a pulse on (Spr) restarts the sun position automatic. 2 = Optimal brightness - no direct sunlight, with as much light as possible. Automatic is activated even when the shading is closed. 3 = Optimal cooling - blocks even more solar radiation, but also results in lower brightness. Automatic is activated even when the shading is closed. 此参数仅在某些配置中可见。 |
- | 0...3 | 1 |
Spi | Sun position automatic interval | 指定在“自动遮阳”控制期间板条调整的频率。 此参数仅在某些配置中可见。 |
min | 1...180 | 120 |
Spos | Sun position automatic start offset | 相对于日出的“太阳位置自动”的起始偏移量。 | min | -90...90 | 30 |
Spoe | Sun position automatic end offset | 相对于日落的“太阳位置自动”的结束偏移量。 | min | -90...90 | -30 |
偏好↑
总结 | 描述 | 数值范围 | 默认值 |
---|---|---|---|
历史记录 | 控制历史记录的条目数。 0:禁用历史记录 控制历史记录跟踪自程序启动以来的相关更改。 |
0...100 | 20 |
使用阳光信息 | 只有当系统变量“阳光”和输入 Sps 处于激活状态时,才会激活自动遮阳。 | - | - |
遮阳设备的类型↑
功能模块和用户界面根据下列类型进行调整:
0:软百叶窗和外百叶窗
1:卷帘和卷百叶窗
2:双向开的窗帘
3: Schlotterer Retrolux(特殊板条可防止阳光直射,因此无需重新调整板条)
4:窗帘向左单方向
5:右向窗帘
6: 雨篷
示例编程↑
一个 Loxone 触控面板连接到 T5 输入,根据 Loxone 的开关标准控制该功能模块。
输出(Op)和(Cl)连接到控制遮阳设备的输出。
参数(Opd)和(Cld)指定运行时间。
参数(Type)定义遮阳设备的类型。
此外,指南针方向在参数(Dir)中被指定,以确保只有在太阳实际照射到窗户上时,才会激活“太阳位置自动”。根据需要,“智能房间控制器”通过输出(Shd)连接到“自动遮阳”模块的输入(Sps)请求遮阳。
当使用软百叶窗时,也必须设置参数 Rd, Bld, Bldo, Sw, Sd,以便正确控制。
功能描述↑
当按照建议的设置进行配置时,当“房间控制器”通过输入(Sps)启用时,“太阳位置自动”就会被激活。然而,如果手动激活“太阳位置自动”,例如通过 App,则不需要来自“房间控制器”的信号。
当太阳到达遮阳区时,“太阳位置自动”开始,在离开遮阳区时结束。
在这段时间内,板条会根据太阳的角度进行调整。最后,百叶窗移动到参数(Spe)所指定的位置。
手动遮阳,与太阳位置无关,可以通过输入(So)或通过 App 中的 "轻微开启 "来触发。然后,板条会在水平方向进行调整。
可以通过输入(DisSp)来停用“太阳位置自动”。
如果在自动模式下手动操作百叶窗(例如使用 App),那么当天的“太阳位置自动”就会被停用。要重新激活自动控制,需要一个脉冲输入(Spr)或通过 App 激活。
当“太阳位置自动”激活时,百叶窗可能不会立即调整。遮阳只根据太阳的位置和相关参数开始。 |
输出(Sp)表示“太阳位置自动”是否激活。
为了同时控制多个百叶窗,需要使用相应的中央功能模块。
如果使用了普通的按键开关或编程了额外的逻辑,则可能需要额外的输入、输出和参数。
方向参数↑
Dir: 遮阳设备相对于地理北方的指南针方向。(0=北,90=东,180=南,270=西)
Dts: 太阳进入遮阳设备时的方向公差。方向公差是相对于遮阳设备的垂直角度而言的。例如,考虑到建筑物的突起物。如果你的遮阳设备不受影响,你可以将其保持在默认值85º。
Dte: 太阳离开遮阳设备时的方向公差。方向公差是相对于遮阳设备的垂直角度而言的。例如,考虑到建筑物的突起物。如果你的遮阳设备不受影响,你可以将其保持在默认值85º。
起始/结束偏移量↑
有了参数(Spos),“太阳位置自动”将在日出后延迟这个分钟数。
这主要与那些可能在日出后不能立刻晒到太阳的窗口来说相关。
有了参数(Spoe),“太阳位置自动”将提前于日落前的这个分钟数。
这与日落前可能受到太阳影响的窗户有关。
这两个参数有两种可能的应用:
日出后和日落前,太阳往往被其他建筑、结构或树木遮挡。在这里,“太阳位置自动”的开始或结束时间可以被调整以适应这些。
另一种可能是改变时间,以便在遮阳打开时可以看到日出或日落。
齿隙时长↑
在调整板条时,如果与先前的运行方向相同,参数(Bld)会加到所需的(Rd)的百分比上。该参数只影响板条调整,因为在启动“太阳位置自动”时,总是需要改变方向。如果板条位置在“太阳位置自动”开始时是正确的,但在一天中变得不准确,必须调整这个参数。
如果与先前的运行方向是相反的,那么在调整板条时,参数(Bldo)会加到所需的(Rd)百分比上。如果在“太阳位置自动”开始时,板条位置已经不正确,(Rd + Bldo)的总和要么太高(太阳照在板条之间),要么太低(百叶窗关闭太多)
对于朝东的窗户,只有一次方向的改变,因为在一天的时间里,板条被打开的次数越来越多;对于朝西的窗户,百叶窗在第一次调整时就会改变方向。
板条调整↑
当“太阳位置自动”激活时,百叶窗的板条会根据太阳的位置进行调整。
板条倾斜的角度可以防止任何太阳光直接进入板条之间。
一般来说,调整是按参数(Spi)设定的间隔进行的,但仅以15°为增量,而且仅在必要时进行。
例如,如果太阳的路径在一个相对恒定的角度,其海拔高度几乎不会改变。基于这个原因,不一定在每个间隔期都进行调整。
当太阳升起时,每隔一段时间就会计算出所需的数值,在必要时调整板条。
当太阳落下时,每隔一段时间就会计算出下一个区间所需的数值,在必要时调整板条。
完全移动、末端位置和剩磁↑
当完全打开百叶窗时(通过 Co、中央功能模块或 App),无论当前位置如何,它们在整个 UP 时间里一直保持激活。这确保百叶窗可以移动到定义的结束位置。这相当于一个参考运行。
但是,出于安全原因,当完全关闭百叶窗时,它们仅在确定的剩余运行时间内激活。
百叶窗的实际位置使用模块的剩磁功能存储在Miniserver中。
例如,如果百叶窗向上移动,然后立即发生电源故障,则迷你服务器无法标记新位置。当电源恢复时,系统将记住百叶窗的先前位置,尽管它们实际上是升起的。
如果随后触发向下移动,则根本不会执行或执行得不完整,因为上一个位置仍被存储。应用程序中显示的状态也与实际位置不匹配。
在这种以及类似的情况下,必须首先执行一个完整的开启运动,然后遮阳将再次按预期运行。
用于设置末端位置的功能↑
自 Loxone Config 12.1 版以来,遮阳技术专家在该模块的可视化中提供了一个功能,用于设置遮阳的末端位置。
此功能可与市面上的设置线相媲美, 并且需要准确了解和遵守相应电机的操作说明。
在块的开放式可视化中,可以在菜单中调用该功能。对于具有完全访问权限的用户,输入密码后即可访问该功能:
通过用户界面启用昼夜节律↑
可通过用户界面手动启动昼夜节律功能,当 太阳位于窗户$时,百叶窗会自动降下。至于是晴天还是阴天,则不予考虑。
时刻表↑
历史记录↑
在用户界面中,可以显示功能块的历史记录。
A maximum of 100 entries can be shown.